Plug-in solar kit sizes: 400 W, 600 W and 800 W (UK)

A kit's size in the UK is the AC rating of its inverter, and the limit is 800 W. The panels can add up to more than that rating. The inverter then cuts a little output at midday, but the extra panels add output in the morning, evening and winter. Each section shows how much for one to four 400 W panels facing south in London and Glasgow, from the same data as the calculator.

400 W AC inverter

A 400 W inverter is under the 800 W limit. The last column shows what share of an 800 W inverter's output it gives with the same panels, in London on a tilted stand. Below 100%, the smaller inverter is holding the panels back.

400 W AC inverter with 400 W panels, south-facing: yearly output
Panels Panel total (W) Within UK limits London, vertical (kWh) London, tilted (kWh) Glasgow, vertical (kWh) Glasgow, tilted (kWh) Cut by the inverter (London, tilted) Compared with an 800 W inverter
1400Yes2914002483350.0%100%
2800Yes5547244786209.4%91%
31,200Yes71389362578625.6%76%
41,600Yes8201,00272989937.3%69%

600 W AC inverter

A 600 W inverter is under the 800 W limit. The last column shows what share of an 800 W inverter's output it gives with the same panels, in London on a tilted stand. Below 100%, the smaller inverter is holding the panels back.

600 W AC inverter with 400 W panels, south-facing: yearly output
Panels Panel total (W) Within UK limits London, vertical (kWh) London, tilted (kWh) Glasgow, vertical (kWh) Glasgow, tilted (kWh) Cut by the inverter (London, tilted) Compared with an 800 W inverter
1400Yes2914002483350.0%100%
2800Yes5827974976680.4%100%
31,200Yes8301,0877179299.4%92%
41,600Yes1,0021,2698741,10920.7%88%

800 W AC inverter

This is the largest inverter the UK rules allow, so the last column reads 100% throughout. The column before it shows how much of the panels' output the inverter cuts at midday, in London on a tilted stand.

800 W AC inverter with 400 W panels, south-facing: yearly output
Panels Panel total (W) Within UK limits London, vertical (kWh) London, tilted (kWh) Glasgow, vertical (kWh) Glasgow, tilted (kWh) Cut by the inverter (London, tilted) Compared with an 800 W inverter
1400Yes2914002483350.0%100%
2800Yes5828004976700.0%100%
31,200Yes8691,1777439901.9%100%
41,600Yes1,1071,4499561,2399.4%100%

"Within UK limits" checks the numbers only: inverter at most 800 W AC, panels at most 2,000 W and four, two in series at most. Panels above 960 W come with advice to consider a professional assessment of the wiring. The UK rules in full · Check your own kit against the limits · Compare two kits side by side · Kits listed on the UK register, with prices

Last updated .